We’ve considered switching to an electric tankless WH. What makes them a poor choice?
Extreme energy use for pretty low deltas on temperature. Best possible efficiency is 100%, far less than the 2.5+ cop a heat pump unit will get you. If it’s at all manageable, get the heat pump.
Frankly, their inefficiency means the emissions they cause are still pretty bad unless you know your energy source is more renewable than most.
But they don’t need venting, which is nice. They do take a big fat electrical connection though - the one I installed was two 2 pole 40a breakers - hopefully you have at least 200A service. Mostly they work as intended.
Most of them are actually coal fired.